China OEM RF mesh Companies –Silver Electrolytic Copper Expulsion Fuse – HolleyDetail:
Spécifications
Produit Tapez |
| EXPULSION FUSE CUT OUT, 27 kV, 150kVBIL, 100 A 8/12kA, 470mm DISTANCE D'FUITE | EXPULSION FUSE CUT OUT, 38kV, 170kVBIL, 100A, 5/8 kA, 660mm CREEPAGE DISTANCE | EXPULSION FUSE CUTOUT, 27kV, 150kVBIL, 200A, 7.1/10 kA, 432mm CREEPAGE DISTANCE | |
Non. | Caractéristiques | Unité | Valeur | Valeur | Valeur |
1 | SOCLE |
| |||
| Modèle | HV1-27/100-8 | HV1-38/100-5 | HV1-27/200-7.1 | ||
| Norme | ANSI/IEEE C 37.40/41/42 CEI60282- 2:2008 | ANSI C-37.40/41/42 and IEC60282-2 | ANSI/IEEE C37.40/41/42 y IEC60282-2:2008 | ||
| Courant nominal | A | 100 | 100 | 200 | |
| Tension nominale | kV | 27 | 38 | 27 | |
| Minimum Short Circuit Current | |||||
| - Symétrique | kA | 8 | 5 | 7.1 | |
| - Asymétrique | kA | 12 | 8 | 10 | |
| Niveau d'isolement minimum : | |||||
| - Impulse withstand voltage (BIL), phase to ground and between phases. | kV | 150 | 170 | 150 | |
| - Withstand voltage at power frequency between phases, dry, 1 min. | kV | 60 | 80 | 60 | |
| - Withstand voltage at power frequency between phase and ground, in wet, 10s. | kV | 50 | 70 | 50 | |
| Insulating porcelain material of the base with high purity alumina compositions (between 94% to 99%) with the addition of vitrifiers. | Oui | Oui | Oui | ||
| Minimum creepage distance (Phase-Earth) | mm | 470 | 660 | 432 | |
| Matériel de contact | Silver electrolytic copper | Silver electrolytic copper | Silver electrolytic copper | ||
| - Minimum thickness of the top contact silver layer (tab) | µm | 15 | 15 | 15 | |
| - Maximum electrical contact resistance between each terminal and the nearest metal part accessible after contact | Ohm | 0.000099 | 0.000099 | 0.000099 | |
| - Upper contact pressure spring with fastening and alignment mechanism | Stainless steel, grade 304 according to AISI 304, DIN 1.4301 | Stainless steel, grade 304 according to AISI 304, DIN 1.4301 | Stainless steel according to AISI 304, DIN 1.4301 | ||
| Matériau des bornes | Cuivre étamé | Cuivre étamé | Cuivre étamé | ||
| -Conductor Range (Diameter) | mm | 4.11-11.35 | 4.11-11.35 | 4.11-11.35 | |
| -Terminals for use with copper or aluminum conductors | Oui | Oui | Oui | ||
| -Type de terminaux | Parallel slots, must include bolt, nuts and pressure washers made of stainless steel | Parallel slots, must include bolt, nuts and pressure washers made of stainless steel | Parallel slots, must include bolt, nuts and pressure washers made of stainless steel | ||
| Top support channel material | Galvanized structural steel | Galvanized structural steel | Galvanized structural steel | ||
| - Galvanized Material Standard | ASTMA575 | ASTMA575 | ASTMA575 | ||
| - Norme de galvanisation | ASTMA153 | ASTMA153 | ASTMA153 | ||
| - Minimum average thickness | µm | 86 | 86 | 86 | |
| Angle d'ouverture minimal | 120° | 120° | 120° | ||
| Minimum number of mechanical operations guaranteed | Non. | 200 | 200 | 200 | |
| Minimum mechanical resistance of the horn for load operation | Dan | 200 | 200 | 200 | |
| Dimensions (See Figure 1) | |||||
| L | mm | 704 | 842 | 704 | |
| M | mm | 409 | 431 | 409 | |
| N | mm | 476 | 567 | 476 | |
| P | mm | 72 | 82 | 72 | |
| Q | mm | 131 | 147 | 131 | |
2 | TUBE PORTE-FUSIBLE | ||||
| Caractéristiques | |||||
| - Norme | ANSI/IEEE C 37.40/41/42 | ANSI/IEEE C 37.40/41/42 | ANSI/IEEE C 37.40/41/42 | ||
| - Tension nominale | kV | 27 | 38 | 27 | |
| - Courant nominal | A | 100 | 100 | 200 | |
| - Minimum symmetrical/asymmetrical short-circuit current | kA | 8/12 | 5/8 | 7,1/10 | |
| - Internal diameter range | |||||
| - minimum | mm | 11.1 | 11.1 | 17.5 | |
| - maximum | mm | 18 | 18 | 23 | |
| - Length (allowable range) | mm | 375 ± 3 | 466 ± 3 | 375 ± 3 | |
| - Metal parts of joining with the base | Bronze coulé | Bronze coulé | Bronze coulé | ||
| - Fuse holder tube cover (top contact) | Silver electrolytic copper, with a minimum thickness of 8 um | Silver electrolytic copper, with a minimum thickness of 8 µm | Silver electrolytic copper, with a minimum thickness of 8 µm | ||
| - Eye hook for pole operation | Cast Bronze, with minimum mechanical resistance of 200daN | Cast Bronze, with minimum mechanical resistance of 200daN | Cast Bronze, with minimum mechanical resistance of 200daN | ||
| - Fuse holder tube material. | Fiberglass with internal coating in moisture-proof vulcanized fiber | Fiberglass with internal coating in moisture-proof vulcanized fiber | Fiberglass with internal coating in moisture-proof vulcanized fiber | ||
| - Fuse holder opening and closing mechanism (fuse holder base) | to avoid fuse holder tube un-alignment greater than 15mm | to avoid holder tube un-alignment no more than 15mm | to avoid fuse holder tube un-alignment no more than 15mm | ||
| Suitable for chicote fuses with removable head (Arc shortening rod) | Oui | Oui | Oui | ||
3 | ACCESSOIRES DE FIXATION | ||||
| - Type de fixation | Type B, according to ANSI/IEEE C37.42 | Type B, according to ANSI/IEEE C37.42 | Type B, according to ANSI/IEEE C37.42 | ||
| - Matériel | Acier galvanisé | Acier galvanisé | Acier galvanisé | ||
| - Norme matérielle | ASTMA575 | ASTMA575 | ASTMA575 | ||
| - Norme de galvanisation | ASTMA153 | ASTMA153 | ASTMA153 | ||
| - Minimum average thickness | µm | 86 | 86 | 86 |
Images de détail du produit :

Guide des produits associés :
Now we have superior devices. Our solutions are exported to your USA, the UK and so on, enjoying a superb name between customers forChina OEM RF mesh Companies –Silver Electrolytic Copper Expulsion Fuse – Holley, The product will supply to all over the world, such as: Australia, Paraguay, Philippines, Due to our strict pursues in quality, and after-sale service, our product gets more and more popular around the world. Many clients came to visit our factory and place orders. And there are also many foreign friends who came for sight seeing, or entrust us to buy other stuff for them. You are most welcome to come to China, to our city and to our factory!