Specifications
DESCRIPTION | UNIT | VALUE | VALUE | VALUE | VALUE | VALUE | VALUE | VALUE | |
1 | GENERAL |
| 1X70mm2 8.7 / 15 (17.5) kV | 1x120mm2, 8.7 / 15 (17.5) kV | 1×150 mm2, 8.7 / 15 (17.5) kV | 1x70mm2, 18/30 (36) kV | 1X120mm2 FOR 18/30 (36) kV | 1×185 mm2, 8.7 / 15 (17.5) kV | 1X185mm2 FOR 18/30 (36) kV |
| Standard |
| NTP IEC 60502-2 | NTP IEC 60502-2 | NTP IEC 60502-2 | NTP IEC 60502-2 | NTP IEC 60502-2 | NTP IEC 60502-2 | NTP IEC 60502-2 |
2 | DESIGNATION N2XSY | 1 x 70 mm2 | 1 x 120 mm2 | 1 x 150 mm2 | 1 x 70 mm2 | 1 x 120 mm2 | 1 x 185 mm2 | 1 x 185 mm2 | |
| Rated Voltage Uo / U (Uo) | kV | 8.7 / 15 (17.5) | 8.7 / 15 (17.5) | 8.7 / 15 (17.5) | 18/30 (36) | 18/30 (36) | 8.7 / 15 (17.5) | 18/30 (36) |
| Maximum temperature under normal conditions | ° C | 90 | 90 | 90 | 90 | 90 | 90 | 90 |
| Maximum short-circuit temperature (5 s. Maximum) | ° C | 250 | 250 | 250 | 250 | 250 | 250 | 250 |
3 | PHASE CONDUCTOR | ||||||||
| Standard | NTP IEC 60228 | NTP IEC 60228 | NTP IEC 60228 | NTP IEC 60228 | NTP IEC 60228 | NTP IEC 60228 | NTP IEC 60228 | |
| Material | Uncoated Annealed Copper | Uncoated Annealed Copper | Uncoated Annealed Copper | Uncoated Annealed Copper | Uncoated Annealed Copper | Uncoated Annealed Copper | Uncoated Annealed Copper | |
| Purity | % | 99.9 | 99.9 | 99.9 | 99.9 | 99.9 | 99.9 | 99.9 |
| Nominal section | mm2 | 70 | 120 | 150 | 70 | 120 | 185 | 185 |
| Class | 2 | 2 | 2 | 2 | 2 | 2 | 2 | |
| Minimum number of wires | No. | 19 | 37 | 37 | 19 | 37 | 37 | 37 |
| Density at 20 ° C | gr / cm3 | 8.89 | 8.89 | 8.89 | 8.89 | 8.89 | 8.89 | 8.89 |
| Electrical resistivity at 20 ° C | Wmm2 / m | 0.017241 | 0.017241 | 0.017241 | 0.017241 | 0.017241 | 0.017241 | 0.017241 |
| Maximum electrical resistance in DC at 20 ° C | Ohm / km | 0.268 | 0.153 | 0.124 | 0.268 | 0.153 | 0.099 | 0.099 |
| Insulation | ||||||||
| Material | XLPE-TR (Tree Retardant Cross-linked Polyethylene) | XLPE-TR (Tree Retardant Cross-linked Polyethylene) | XLPE-TR (Tree Retardant Cross-linked Polyethylene) | XLPE-TR (Tree Retardant Cross-linked Polyethylene) | XLPE-TR (Tree Retardant Cross-linked Polyethylene) | XLPE-TR (Tree Retardant Cross-linked Polyethylene) | XLPE-TR (Tree Retardant Cross-linked Polyethylene) | ||
| Colour | natural | natural | natural | natural | natural | natural | natural | ||
| Average nominal thickness | mm | 4.5 | 4.5 | 4.5 | 8 | 8 | 4.5 | 8 | |
| Screen |
|
|
|
|
|
|
|
|
| Semiconductor tape or extruded compound semiconductor on the conductor | YES | YES | YES | YES | YES | YES | YES | ||
| About the insulator | |||||||||
| Semiconductor tape or extruded composite semiconductor | YES | YES | YES | YES | YES | YES | YES | ||
| Copper wire braided mesh or tape with resistance less than 3 ohm/km at 20 ° C |
| YES | YES | YES | YES | YES | YES | YES |
| Sheath | |||||||||
| Material | PVC –ST2 | PVC – ST2 | PVC – ST2 | PVC –ST2 | PVC – ST2 | PVC – ST2 | PVC – ST2 | ||
| Colour | Red | Red | Red | Red | Red | Red | Red | ||
| Minimal thickness | mm | 1.2 | 1.2 | 1.3 | 1.4 | 1.5 | 1.4 | 1.6 | |
| Tests |
|
|
|
|
|
|
|
|
| Insulation Continuity Test Voltage | kV | 30.5 | 30.5 | 30.5 | 63 | 63 | 30.5 | 63 | |
| Insulation construction process | Through simultaneous triple extrusion process | Through simultaneous triple extrusion process | Through simultaneous triple extrusion process | Through simultaneous triple extrusion process | Through simultaneous triple extrusion process | Through simultaneous triple extrusion process | Through simultaneous triple extrusion process |
Choosing Holley’s Medium Voltage Copper Cable is not just an investment in immediate performance but also in long-term reliability and sustainability. By minimizing energy losses through efficient conductivity, our cables contribute to the overall efficiency of PV strings, supporting sustainable energy generation. This commitment to sustainability is matched by our dedication to customer satisfaction. We understand the importance of reliability in renewable energy applications, and our cables are tested to meet rigorous industry standards. Benefit from a reduced carbon footprint and enhanced system longevity with our expertly engineered copper cables.Discover the difference with Holley's Medium Voltage Copper Cable and elevate your PV string systems to new heights of efficiency and dependability.