Specifications
DESCRIPTION | UNIT | VALUE | VALUE | VALUE | VALUE | VALUE | |
1 | GENERAL |
| 3×35 + 1×16 + NA25 mm2 | 3×50 + 1×16 + NA35mm2 | 3×70 + 1×16 + NA50 mm2 | 3×25 + 1×16 + NA25 mm2 | 3X120 + 1X16 + NA70 mm2 |
| Manufacturing standard |
| NTP 370.254 | NTP 370.254 | NTP 370.254 | NTP 370.254 | NTP 370.254 |
2 | DESIGNATION | CAAI | CAAI | CAAI | CAAI | CAAI | |
| Rated Voltage Uo / U | kV | 0.6 / 1 | 0.6 / 1 | 0.6 / 1 | 0.6 / 1 | 0.6 / 1 |
3 | TERMS OF USE | ||||||
| Maximum temperature in permanent regime. | ° C | 90 | 90 | 90 | 90 | 90 |
| Maximum temperature in overload regime. | ° C | 130 | 130 | 130 | 130 | 130 |
| Maximum temperature in short-circuit mode (5 s) | ° C | 250 | 250 | 250 | 250 | 250 |
4 | CABLES GATHERING: | ||||||
| Maximum wireways, depending on the diameter of thePhase wire | Times | 60 | 60 | 60 | 60 | 60 |
5 | PHASE CABLE: | ||||||
| Standard | NTP IEC 60228 | NTP IEC 60228 | NTP IEC 60228 | NTP IEC 60228 | NTP IEC 60228 | |
| Material | Pure uncoated aluminum | Pure uncoated aluminum | Pure uncoated aluminum | Pure uncoated aluminum | Pure uncoated Aluminum | |
| Nominal section | mm2 | 35 | 50 | 70 | 25 | 120 |
| Class | 2 | 2 | 2 | 2 | 2 | |
| Minimum number of wires | No. | 7 | 6 | 12 | 6 | 15 |
| Maximum electrical resistance in DC at 20 ° C | Ohm / km | 0.868 | 0.641 | 0.443 | 1.20 | 0.253 |
| Insulation | ||||||
| Material | Cross-linked polyethylene XLPE | Cross-linked polyethylene XLPE | Cross-linked polyethylene XLPE | Cross-linked polyethylene XLPE | Cross-linked polyethylene XLPE | ||
| XLPE requirement | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | ||
| Minimum content of carbon black in XLPE | % | 2 | 2 | 2 | 2 | 2 | |
| Minimum average thickness | mm | 1.14 | 1.52 | 1.52 | 1.14 | 2.03 | |
| Minimum thickness at one point | mm | 1.03 | 1.37 | 1.37 | 1.03 | 1.83 | |
6 | STREET LIGHT CABLE | ||||||
| Standard | NTP IEC 60228 | NTP IEC 60228 | NTP IEC 60228 | NTP IEC 60228 | NTP 370.250 | |
| Material | Pure Aluminum without Coating | Pure uncoated aluminum | Pure uncoated aluminum | Pure uncoated aluminum | Pure uncoated aluminum | |
| Nominal section | mm2 | 16 | 16 | 16 | 16 | 16 |
| Class | 2 | 2 | 2 | 2 | 2 | |
| Minimum number of wires | No. | 7 | 6 | 6 | 6 | 6 |
| Maximum electrical resistance in DC at 20 ° C | Ohm / km | 1.91 | 1.91 | 1.91 | 1.91 | 1.91 |
| Insulation | ||||||
| Material | Cross-linked polyethylene XLPE | Cross-linked polyethylene XLPE | Cross-linked polyethylene XLPE | Cross-linked polyethylene XLPE | Cross-linked polyethylene XLPE | |
| XLPE requirement | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | |
| Minimum content of carbon black in XLPE | % | 2 | 2 | 2 | 2 | 2 |
| Minimum average thickness | mm | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 |
| Minimum thickness at one point | mm | 1.03 | 1.03 | 1.03 | 1.03 | 1.03 |
7 | NEUTRAL CABLE SUPPORT | ||||||
| Standards | NTP 370.258 | NTP 370.258 | NTP 370.258 | NTP 370.258 | NTP 370.258 | ||
| Cable Material | Aluminium alloy | Aluminium alloy | Aluminium alloy | Aluminium alloy | Aluminium alloy | ||
| Conductivity | % IACS | 52.5 | 52.5 | 52.5 | 52.5 | 52.5 | |
| Nominal section | mm2 | 25 | 35 | 50 | 25 | 70 | |
| Number of wires | 7 | 7 | 7 | 7 | 7 | ||
| Wire diameter | mm | 2.13 | 2.52 | 3,023 | 2.13 | 3.57 | |
| Minimum tensile strength | kN | 7.72 | 10.81 | 15.44 | 7.72 | 20.95 |
| Nominal Mass | kg / km | 68.4 | 95.7 | 136.8 | 68.4 | 191.5 |
| Density at 20 ° C | kg / m3 | 2703 | 2703 | 2703 | 2703 | 2703 |
| Electrical resistivity at 20 ° C | Ωmm2 / m | 0.032840 | 0.032840 | 0.032840 | 0.032840 | 0.032840 |
| Maximum electrical resistance in DC at 20 ° C | Ω / km | 1.3511 | 0.9651 | 0.6755 | 1.3511 | 0.4825 |
| Insulation | ||||||
| Material | Cross-linked polyethylene XLPE | Cross-linked polyethylene XLPE | Cross-linked polyethylene XLPE | Cross-linked polyethylene XLPE | Cross-linked polyethylene XLPE | ||
| XLPE requirement | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | ||
| Minimum content of carbon black in XLPE | % | 2 | 2 | 2 | 2 | 2 | |
| Minimum average thickness | mm | 1.14 | 1.14 | 1.52 | 1.14 | 1.52 | |
| Minimum thickness at one point | mm | 1.03 | 1.03 | 1.37 | 1.03 | 1.37 |
Our Self-Supporting Aluminum Cable is available in a variety of specifications to meet the specific needs of different installations. For enhanced versatility, options include compositional configurations such as 3×35 + 1×16, 3×50 + 1×16, and 3×70 + 1×16, among others, with cross-sectional areas measured in mm² ranging from 25 to 70 mm². These variations facilitate flexibility in installation while supporting the demanding power requirements of a microgrid PV power station. Each variation is designed with a specific focus on maximizing efficiency and minimizing maintenance, thus providing long-term value and stability to your energy projects.Investing in premium-quality cables for your microgrid PV power station is crucial for optimizing overall system efficiency and sustainability. Our self-supporting aluminum cables are not just conduits for electricity; they represent a commitment to high performance and eco-friendly energy solutions. By opting for our product, you can achieve substantial improvements in infrastructure resilience and energy security, significantly contributing to the sustainability goals of your power generation projects. Choose Holley for a reliable, efficient, and future-ready infrastructure that empowers your microgrid PV power station to deliver peak performance.